01 ACTUAL SIGNALS

01.02 MOTOR SPEED FILT
01.03 FREQUENCY
01.04 CURRENT
01.05 TORQUE
01.06 POWER
01.07 DC BUS VOLTAGE
01.08 MAINS VOLTAGE
01.09 OUTPUT VOLTAGE
01.10 ACS800 TEMP
01.14 OP HOUR COUNTER
01.15 KILOWATT HOURS
01.16 APPL CODE DUTY
01.17 DI6-1 STATUS
01.18 AI1 [V]
01.19 AI2 [mA]
01.20 AI3 [mA]
01.21 RO3-1 STATUS
01.22 AO1 [mA]
01.23 AO2 [mA]
01.28 AO3 [mA]
01.29 AO4 [mA]
01.35 MOTOR 1 TEMP
01.36 MOTOR 2 TEMP
01.37 MOTOR TEMP EST
01.38 AI5 [mA]
01.39 AI6 [mA]
01.40 DI7-12 STATUS
01.41 RO4-7 STATUS
01.43 MOTOR RUN-TIME
01.44 FAN ON-TIME
01.45 CTRL BOARD TEMP
02 ACTUAL SIGNALS
02.01 SPEED REF 2
Actual signals and parameters
Description
Basic signals for monitoring of the drive.
Calculated motor speed in rpm. 100% corresponds to
REF1 MAXIMUM.
Calculated output frequency.
Measured motor current.
Calculated motor torque. 100% is the motor nominal torque.
Motor power. 100% is the nominal power.
Measured intermediate circuit voltage.
Calculated supply voltage.
Calculated motor voltage.
Calculated IGBT temperature. 100% is the trip point
Elapsed time counter. Runs when the control board is powered.
kWH counter.
Control program code load.
Status of digital inputs. Example: 000001 = DI1 is on, DI2 to DI6 are
off.
Value of analog input AI1.
Value of analog input AI2
Value of analog input AI3
Status of relay outputs. Example: 001 = RO1 is energized, RO2 and
RO3 are de-energized.
Value of analog output AO1.
Value of analog output AO2.
Value of output 1 of the Analog I/O Extension module (optional).
Value of output 2 of the Analog I/O Extension module (optional).
Measured temperature of motor 1. See
Measured temperature of motor 2. See
Estimated motor temperature.
Value of input 1 of the Analog I/O Extension module (optional).
Value of input 2 of the Analog I/O Extension module (optional).
Status of digital inputs of the Digital I/O Extension modules (optional). 1 = 1
Status of digital outputs of the Digital I/O Extension modules (optional). 1 = 1
Motor run time counter. The counter runs when the inverter
modulates.
Running time of the drive cooling fan.
Note: The counter can be reset by the DriveWindow PC tool.
Resetting is recommended when the fan is replaced.
Control board temperature.
Speed and torque reference monitoring signals and control program
values.
Limited speed reference. 100% corresponds to
MAXIMUM.
11.05
EXT
35.01
MTR1 TEMP SEL.
35.04
MTR2 TEMP SEL.
11.05
EXT REF1
FbEq
200 = 1%
100 = 1 Hz
10 = 1 A
100 = 1%
10 = 1%
1 = 1 VDC
1 = 1 VAC
1 = 1 VAC
10 = 1%
1 = 1 h
1 = 100 kWH
1 = 1%
1 = 1
1000 = 1 V
1000 = 1 mA
1000 = 1 mA
1 = 1
1000 = 1 mA
1000 = 1 mA
1000 = 1 mA
1000 = 1 mA
o
1 = 1
C
o
1 = 1
C
o
1 = 1
C
1000 = 1 mA
1000 = 1 mA
1 = 10 h
1 = 10 h
o
1 = 1
C
200 = 1%