Table of Contents

Advertisement

3. See 1. Output is activated when the specified alarm point or Zone is in alarm.
4. See 1. Quantity (1-9): "1" means one unit in alarm is required, "2" means two units
in alarm are required to activate the output and so on.
5. Pre-warning.
warning level. For more information regarding pre-warning, see FT1020G3
Operation Manual.
6. See 5. Output is activated when the specified alarm point exceeds the pre-warning
level
7. See 5. Output is activated when the specified alarm point or zone exceeds the pre-
warning level
8. See 5. See also 4 above regarding "Quantity".
9. Heavy smoke / heat alarm. Output is activated when the specified Zone exceeds
the heavy smoke / heat level. For more information regarding heavy smoke / heat
alarm, see FT1020G3 Operation Manual.
10. See 9. Output is activated when the specified alarm point exceeds the heavy smoke
/ heat level.
11. See 9. Output is activated when any alarm point exceeds the heavy smoke / heat
level.
12. See 9. See also 4 above regarding "Quantity".
13. Output is activated when only one address (in two- address dependence) is in fire
alarm state. For more information, see FT1020G3 Operation Manual.
14. Output is activated when only one zone (in two-zone dependence) is in fire alarm
state. For more information, see FT1020G3 Operation Manual.
15. Output activated when "Multiple detector alarm" is true, i.e. fire alarm type A.
16. Output activated when "One detector alarm" is true, i.e. fire alarm type B
17. General Key cabinet alarm activated. For more information, see FT1020G3
Operation Manual.
18. Alarm Acknowledgement Facility, requires Alarm Acknowledgement Module
AAM. "Alarm" is activated in the specified AAFC zone. Panasonic new Local Alarm
Acknowledgment (LAA) is typically Brooks AAM.
19. Output activated for any "Quiet alarm" in the specified zone. Normally used in
AS1668 fire fan applications or as a non-latching / non-brigade call alarm.
20. Output activated for one specified "Quiet alarm" in the specified zone-address.
Used in AS1668 fire fan control applications.
21. This control expression is true (i.e. output activated) for 15 seconds after the last
alarm is reset.
22. Output of specified Zone-Address is activated for predetermined time (set in
EBLWin system properties). Typical application when a smoke detector is
programmed to activate 3379. If the smoke is cleared during the delay time, the
sounder base will de-activate otherwise, a general alarm in FT1020G3 will be
activated.
23. Same as 22 but for a specified zone.
24. Same as 22 but for any Zone or Zone-Address in the system..)
25. Output is activated only if the first alarm is an alarm in the specified Zone in the
specified Control Unit. NOTE: This is not valid for manual call points.
96
The trigger condition is true as long as the pre-warning level is exceeded. It is also true as long as the fire alarm level is
exceeded even if the option pre-warning detection is disabled (via EBLWin).
97
See chapter "Fire alarm type A and Fire alarm type B", page 119.
96
Output is activated when the specified alarm point exceeds the pre-
89
Technical/Programming Manual
FT1020G3 Rev 2.2.1