16. Activated Extinguishing equipment feedback to the FT1020G3 Control Unit to light
up the LED "Extinguishing".
17. External fuses (for external. power supply equipment) fault output will activate a
fault in the FT1020G3 system. The following fault message will be shown:
FAULT: External fuses,
Control Unit xx
18. External power supply equipment fault output will activate a fault in the FT1020G3
system. The following fault message will be shown:
FAULT: External power supply,
Control Unit xx
19. Activated input (i.e. fault on the fault routing equipment) will generate a fault in
FT1020G3:
FAULT: Fault warning routing equipment,
Control Unit xx
20. A special detector, push button, etc. can activate a fire alarm in FT1020G3. Zone
no. and Address (+ user definable alarm text).
21. A feed-back from the equipment activated by the corresponding interlocking output.
Activated input is shown in menu H9/C1. See also chapter "Interlocking function",
page 96.
22. "Loss of the battery charger to external power supply equipment" fault output will
activate a fault in the FT1020G3 system. It will have the same time delay, as set
for the Loss of main power source fault for the CIE The following fault message
will be shown:
FAULT: Charging external power supply,
Control Unit xx
23. "Loss of main power source to external power supply equipment" fault output will
activate a fault in the FT1020G3 system. It will have the same time delay, as set
for the Loss of main power source fault for the CIE The following fault message
will be shown:
FAULT: Mains, external power supply,
Control Unit xx
24. Default. Indicating that an input trigger condition is not selected, i.e. the input will
not "activate" anything.
25. Used for the "outside switch" (Bulgin key) (i.e. the New Zealand FB silence switch).
Turned on: Alarm devices and the CIE buzzer will be disabled. The following fault
message will be shown:
FAULT: FB Silence switch,
Control Unit xx
From Turned on to Turned off: All fire alarms will be isolated, all zones in alarm
will be disabled, alarm devices and the CIE buzzer will be re-enabled and the fault
will be serviced.
Technical/Programming Manual
81
77
FT1020G3 Rev 2.2.1