System Charge Adjustment; Charging: Weigh-In Method; Subcooling Charging And Refrigerant Adjustment In Cooling; (Above 55°F Outdoor Temp.) - Bosch 19 SEER Series Operation Manual

Inverter ducted packaged heat pump
Table of Contents

Advertisement

2 0 | Bosch Inverter Ducted Packaged Heat Pump

12 System Charge Adjustment

      T he unit comes precharged from the factory with 12-9 lb-oz of
refrigerant. Please measure superheat and subcooling, and add
or remove refrigerant accordingly.

12.1 Charging: Weigh-In Method

Weigh-in method is recommended for the initial installation, or anytime
a system charge is being replaced. Weigh-in method can also be used
when power is not available to the equipment site or operating conditions
(indoor/outdoor temperatures) are not in range to verify with the
subcooling charging method.
Heat Pump Model
BRB-60HWD1N1-M19
Table 10

12.2 Subcooling Charging and Refrigerant Adjustment In Cooling

(Above 55°F Outdoor Temp.)
1.
Check the outdoor ambient temperatures.
Subcooling (in cooling mode) is the only recommended method of
charging above 55°F outdoor ambient temperatures. For outdoor
ambient temperatures below 55°F , use weigh-in charge method.
  I t is important to return in the spring or summer to accurately
charge the system in the cooling mode when outdoor ambient
temperature is above 55°F.
Outdoor
Temperature
Above 55ºF
120ºF
55ºF
Outdoor Temp1
Figure 22
For best results the indoor temperature should be kept between 70°F to
80°F.
Data subject to change
Refrigerant Charge (lb-oz)
12-9
Outdoor
Temperature
Below 55ºF
55ºF
Outdoor Temp2
80 ºF
70ºF
Figure 23
2.
Stabilize the system.
After starting the system in cooling mode, short press "FORCE"
3.
button, and a "    | — " symbol should appear. System may take 10
minutes to ramp up. Operate the system for a minimum of twenty
(20) minutes.
SW2
FORCE
Figure 24
      A fter a twenty (20) minute stabilization period operating at
100% capacity (60 Hertz ), maintain continuous operation while
adjusting refrigerant charge. After adjusting, operate system for
a minimum of fi ve (5) minutes for system to stabilize, otherwise
repeat step 3.
20 MIN.
Figure 25
4.
Calculate subcooling value on liquid line (According to Table 11)
Measured Liquid Line Temp. = ________ºF
Measured Liquid Line Pressure = _______ PSIG
Calculate subcooling value = ________ºF
Installation & Operation Manual
Indoor Temp
03.2019 | BTC 761701105 A