Airfl Ow Performance - Bosch 19 SEER Series Operation Manual

Inverter ducted packaged heat pump
Table of Contents

Advertisement

Installation & Operation Manual
5 Airfl ow Performance
Airfl ow performance data is based on cooling performance with a coil and
no fi lter in place. Check the performance table for appropriate unit size
selection.
External static pressure should stay within the minimum and maximum
limits shown in the table below in order to ensure proper operation of
both cooling, heating, and electric heating operation.
Model
Motor Speed
Number
Tap 1
Tap 2 -Default Log Stage Setting
60
Tap 3
Tap 4 -Default High Stage Setting
Tap 5
Table 6
B old outlined areas represent airfl ow outside of the required 300-450 cfm/ton
   
range.
NOTES:
1.
The high stage airfl ow must be used as the rated airfl ow for the full load
operation of machine.
2.
The rated airfl ow of systems without electric heater kits requires between
300 and 450 cubic feet of air per minute (CFM).
3.
The rated airfl ow of systems with electric heater kits requires between 350
and 450 cubic feet of air per minute (CFM).
4.
The air distribution system has the greatest eff ect on airfl ow. Therefore, the
contractor should use only industry-recognized procedures.
5.
Duct design and construction should be carefully done. System
performance can be lowered dramatically through poor design or
workmanship.
6.
Air supplier ducts should be located along the perimeter of the conditioned
space and properly sized. Improper location or insuffi cient air fl ow may
cause drafts or noise in the ductwork.
7.
Installers should balance the air distribution system to ensure proper quiet
airfl ow to all rooms in the home. An air velocity meter or airfl ow hood can be
used to balance and verify branch and system airfl ow (CFM).
BTC 761701105 A | 03.2019
0[0]
0.1[.02]
0.2[. 05]
SCFM
1385
1300
1230
164
Watts
171
180
SCFM
1432
1352
1489
1.8
1.89
Watts
1.76
SCFM
1843
1782
1711
Watts
343
362
377
SCFM
1964
1903
1840
435
450
Watts
466
SCFM
2247
2339
2307
Watts
695
707
Bosch Inverter Ducted Packaged Heat Pump | 13
SCFM
External Static Pressure-Inches W.C.[kPa]
0.3[.07]
0.4[.10]
0.5[.12]
1136
1045
959
192
204
217
1279
1172
1088
1.96
2.02
2.13
1639
1572
1497
390
400
411
1786
1724
1655
479
494
507
2204
2135
2056
725
734
747
746
0.6[.15]
0.7[.17]
0.8[.20]
867
787
717
232
238
249
1013
934
863
2.24
2.34
2.43
1409
1341
1271
427
440
456
1591
1488
1427
551
521
535
1922
1800
1659
737
719
686
Data subject to change