Siemens SIPROTEC 5 Technical Data Manual page 104

High-voltage bay controller, v7.80 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

11.35
Synchronization Function
Operating Modes
Synchrocheck
Switching synchronous systems
Switching asynchronous systems
De-energized switching
Direct closing command
Setting Values
Supervision/Delay times:
Max.durat. sync.process
Supervision time de-energized
switching
Closure delay
Voltage threshold values:
Upper voltage limit V
Lower voltage limit V
V<, for off-circuit conditions
V>, for voltage present
Differential values, changeover thresholds asynchronous/synchronous/balancing.:
Voltage differences
V2 > V1; V2 < V1
Frequency difference f2 > f1;
f2 < f1
Angle difference α2 > α1; α2 < α1
Adjustments of the sides:
Angle adjustment
Voltage adjustment
Circuit breaker
Closing time of the circuit breaker
Dropout Ratio
Min./max. operating limit
Voltage differential
De-energized/energized
Frequency difference
Angle difference
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
0.00 s to 3 600.00 s or ∞ (ineffec-
tive)
0.00 s to 60.00 s
0.00 s to 60.00 s
0.300 V to 340.000 V (phase-to-
max
phase)
0.300 V to 340.000 V (phase-to-
min
phase)
0.300 V to 170.000 V (phase-to-
phase)
0.300 V to 340.000 V (phase-to-
phase)
0.000 V to 170.000 V
0.000 Hz to 2.000 Hz (synchro-
nous)
0.000 Hz to 4.000 Hz (asynchro-
nous)
0
o
to 90
o
0.0
o
to 360.0
0.500 to 2.000
0.01 s to 0.60 s
1 % of the setting value
10 % of the setting value or 0.5 V
5 % of the setting value
3 mHz
0.1
o
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.001 V
Increments of 0.001 V
Increments of 0.001 V
Increments of 0.001 V
Increments of 0.001 V
Increments of 0.001 Hz
Increments of 1
o
Increments of 0.1
Increments of 0.001
Increments of 0.01 s
Technical Data
11.35 Synchronization Function
o
o
1199

Advertisement

Table of Contents
loading

This manual is also suitable for:

6md856md86

Table of Contents