General Device Data - Siemens SIPROTEC 5 Technical Data Manual

High-voltage bay controller, v7.80 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

11.1

General Device Data

Analog Inputs
11.1.1
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Input and output modules
Measuring range
Input impedance
Thermal rating
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Insulation class
Connector type
Differential current input channels
Measuring range
Fault
Input impedance
Conversion principle
Permissible potential difference
between channels
Galvanic separation from ground/
housing
Permissible overload
Measurement repetition
Measuring-Transducer Inputs (via Module ARC-CD-3FO)
Connector type
Number of transceivers
Fiber type
Receiver
Maximum
Minimum
Spectrum
Attenuation
Optical budget
Analog sampling rate
ADC type
Transmitter
Type
Wavelength
Transmit power
Numerical aperture
Signal rate connection test
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
50 Hz, 60 Hz
rated
IO202, IO208, IO211, IO214
0 V to 200 V
< 0.1 VA
230 V continuously
SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
8-pin multiple contact strip
4
DC -24 mA to +24 mA
< 0.5 % of the measuring range
140 Ω
Delta-sigma (16 bit)
DC 20 V
DC 700 V
DC 100 mA continuously
200 ms
AVAGO AFBR-4526Z
3
Polymer Optical Fiber (POF) 1 mm
-10 dBm ± 2 dBm
-40 dBm ± 2 dBm
400 nm to 1100 nm
In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m Additional attenuation comes from the plug and sensor head.
Minimal 25 dB
1
16 kHz
10-bit successive approximation
LED
λ = 650 nm
Minimum 0 dBm
Maximum 2 dBm
0.5
2
1 pulse per second
Technical Data
11.1 General Device Data
IO215
0 V to 7.07 V
< 0.01 VA
20 V continuously
1105