Control Air M/M+ Water To Water Applications; The Control Air M And M+ Screens; Units Status Screen/Home Page; Settings Screen - Bosch Control Air M Installation & Operation Manual

For commercial water to water ddc applications
Table of Contents

Advertisement

1 4 | Control Air M/M+ Water to Water Applications

9 The Control Air M and M+ Screens

9.1 Units Status Screen/Home Page

The Unit Status screen (Figure 14) is the home page for the Control Air
M, and shows the main menus/categories of the software the user can
interface with on the devices.
Settings – For an installer, these settings allow for changes to
the device, as well as unit configuration at start-up.
Service – For a service technician, this menu allows a user to
diagnose or troubleshoot the unit.
The screen provides valuable unit diagnostic data - entering and leaving
water temperatures, states of the compressors, Reversing valve, Pump.
It gives the user the ability to change the temperature units between
Fahrenheit and Celsius. The header of the screen is common to most
screens.
Figure 14

9.2 Settings Screen

The Settings page allows the user to access one of the following pages:
Unit Settings
Device Settings
Alarm Settings
*Pumps
Temperature
Schedule
Setpoints
*Lead/Lag
*
If confi gured in Unit Settings.
Figure 15
Data subject to change

9.2.1 Unit Settings Screen

This screen can be accessed from the Settings menu. This menu allows
the commissioning agent to setup or modify operational parameters of the
unit.
Once all operational parameters are confi gured, these settings may be
saved and archived to fl ash memory by selecting the Save Settings check-
box.
Figure 16
Occupancy Command
Under the Unit Settings screen, this parameter is used to select the
control source that will provide the occupancy command to the unit. The
options for this variable are the following:
Digital Input
Local Schedule
BAS Command
Manual Override
Throughout the setup process, by selecting diff erent boxes, this
is how you advance to the next setup screen if available, while
the back arrow is used to backtrack to previous screens.
Digital Input: The Digital Input option may be selected if the unit
occupancy is required to be controlled remotely via a switch (dry
contact) or other binary input. The connection (typically from a room
occupancy sensor) should be made in IN-1 of the controller. Choosing
this setting allows the unit to be placed in occupied mode once the
input is shorted to ground, and in unoccupied mode once the input is
opened.
Local Schedule: Schedule runs the unit on a local, modifi able
schedule, which cannot be accessed over a network. The occupancy
schedule for heating or cooling can be set according to the morning,
daytime, and night time settings for each day of the week. The option
will allow the unit to run on an 8:00 AM to 5:00 PM default schedule
everyday if the unit is to be started up during the construction phase of
the project. See the Schedule Screen for more information.