Shunt-Tripping Device; Bell Alarm And Lockout Device; Replacement Of Coil - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

GEK-7303
Low Voltage Power
Circuit Breakers
2
3
4
5.
I
.
I
-----{;}
.
.
6
Fig. 45
SHUNT-TRIPPING DEVICE
(FIG. 45)
II
•,
II
~
)
-$
a
(0133C90?
1)
The shunt
tripping device
is mounted on a
bracket attached to the
left
side of the operating
m.echanism
(looking
from the front).
·
A remote switch or
relay
contacts are used
to close the circuit of the device causing the
ar_ma_ture
(9)
to engage the trip paddle (11), thereby
tr1ppmg
the
breaker. The spring (2)
is
used to
return the armature to the neutral position after
the
breaker trips.
To prevent overheating, the coil (7) is cut
off by contacts of the
auxiliary
switch which
are open when the breaker is open.
ADJUSTMENTS
From 1/32 in; to
1/16-in.
over-travel of the
armature ~s required when the breaker is tripped.
If
any adJustment
is
necessary to provide this
amount of overtravel, the
trip
lever is bent in
or out accordingly.
REPLACEMENT OF COIL
(Fig. 45)
1.
Di.
s connect
leads
to coil (7).
2.
Remove magnet (6) and coil from frame
(3).
10
9
I.
SPRING
8
2. PIN
3.
FRAME
4.
WEIGHT
5. SCREWS
.
6.
MAGNET
7. COIL
8. CLAMP
9.
ARMATURE
10. ARMATURE ARM
1
.
II.
TRIP PADDLE
12
..
CLAMP
Shunt tripping device
3.
Bend
lower
end of clamp (8) straight
and remove.
4.
Remove coil anq install new coil in
re-
verse order.
BELL ALARM AND
LOCKOUT DEVICE
(FIG.
46)
The device operating link (2)
is·
engaged with
the breaker crossbar side-link pin (1), thereby
operating the device whenever the breaker is
tripped by the overcurrent trip devices, the under-
voltage device or the drawout trip interlock.
The
shunt trip device and the manual trip button
will defeat the device. The bell alarm and
lockout
device can be reset only by the manual trip button
on the front escutcheon.
If
the
lockout
device
is omitted, the device can
.
be reset by manual
trip button or
by·
closing the breaker, provided
the fault has been eliminated.
Adjustments
1.
Adjust the bell alarm-device latch (4) so
that a clearance of 1/16 in.
:t;
1/64 in. is main-
tained with the catch (15) when the breaker
is
closed.
2.
With the breaker fully open, adjust
the
device adjusting screw (12), on the operating
arm (13), for
an
overtravel of
1/16 to 3/32
of
an in. after the device contacts are just touching
This will assure that
the
device is operated when the