Selective Tripping; Typical Time-Current Characteristics For Overcurrent Trip Devices - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

3.
On
drawout breakers wired
for the
fourth
gr·
o und sensor
coil,
unsolder
external
sensor coil
leads
at terminal
board
on female disconnect
plug.
On stationary
breakers unsolder
twisted
shielded pair from Terminal
Board
(Fig.
40).
4~
Remove
the four bolts connecting
each
·
coil as·sembly
to
the
pole
unit.
5.
Remove the
coil assemblies taking care
not
to
damage
the inter-connecting
coil wires.
·
6.
No
further
breakdown of the
.coil
assem-
blies should
be made.
Do not
remove the coils
from around their iron
core.
7.
·
Replace
coil
assemblies
in
reverse
order.
Sensor
Coils
(Al_{-3-75/100)
Only
(Fig. 33)
1.
Disconnect
control
plug between
Power
Supply
Unit and
Sensor
Coils.
2.
If
present, disconnect
fourth
ground
sensor
coil
lead as
described in Step
3 above.
3.
Disconnect
·resistor
board from back frame
by removing
two
nuts
from
studs
welded
to
back
frame.
Remove
the two
remaining hex head
bolts
and
nuts.
Lift
board
from the two
studs.
·
4.
Remove
collar at
end of primary dis-
connects by
loosening
two allen
head
bolts and
sliding off collar.
. ~
100 0
I
J
J
11
I
I
_I
I
I
N.ONO•TIU
DELAY Pffl~'i'!.:A0..USW11..E
0
,
,Oa,.
Tri
,.,.__.
_11
.!!JlN~
so
200
10 0
0
~--
0
~
MAXNUM
BREA!(£"
~i:::~
:,.:I' '
0..£AIING•TIME
0
,
....
.....
':
~
.....
l'~
0
TIME
AD.IUSTUL(
,
~
[-...
i~=~:.-;.s:,;1~0A
~
r::,..
z~P(C:TMl.T)ATIOO\:
~
LOIIO
I
noc
ff i"ir-'
l'
I
IIINIW~~
REl<T
TWt
.s
NsnJmu.rous
PIC:IMP
SET
N
FACTORY-
i,..
4
TO"
nc.
s
.t
BRCAl«R RA
.,
I)
z
I
.o
.o
'
f:::
~
;:
IWO- IRCAl<[R
1/Ql'(RATIIG• tlM
C
~
~
~
~
~
N
~
~
f;S::
~
.a
z s
4
u
io
zo
oo
ioo
aoo
CURRENT IN TIMES BREAKER RATING
Low
Voltage
Power Circuit
Breakers GEK-7303
5.
Work
coils
toward
end of
stud.
Starting
with one outside
pol
e, slip
coils off stud
and
onfo
your
right
arm
or properly supported
cyl-
inder, now move to
center
pole ~d O?t
s
ide
.Pole
until
coils are removed place coils with resistor
board
on
clean flat
surface.
When
removing coils
from your arm be careful
not to
break or
f?ul
interconnecting coil wires.
Also note location
of spacers. Spaces may vary in thickness their
·
purpose is to space coils
out
. for a firm fit.
SELECTIVE TRIPPING
.
Selective
tripping
is obtained
when the breakers
in
the electrical a1str1out1on
system
are
arranged
on
the
basis of
a
progressive series
of
time
avd
current
pickup.
This will allow
the
breaker having
the shorter time
setting
and
the
1ower
pickup
to trip
before the breaker having the
longer
time
setting and the higher
current
pickup, provided
the fault is
on
the
·
part of
the line protected
by
the breaker
having the lower setting.
Hence, if
a
fault
occurs
in any part of the
electrical
system,
only
the breaker nearest
the
fault will
trip.
In
order
to reduce .the possibility of damaging
the
equipment
and
to provide maximum safety to
the
operator,
the
overload
caused by
a.
fault
is
removed in a minimum
amount
of time by
selec-
tive tripping. Overloads producing current up to
five or ten times the
breaker
rating are
r
emoved
in
a matter of
a few
cycles while currents in
excess of this
value
are
remqved instantaneously.
---
kJ
11111
I
I
I
HG
'TW[
OCI.
11
P<Cl<•UI'
ADJUST
ABU
FROM
a
TO
1 .ITll<CS
8RCAl<l'.R1Up,.._
1000
soo
200
1,,1111£. AO.N$TAIR.[
I
N
IM:fOrtr-
\
1
·
so,o,.oAs
sa:ac>SUA
~
'
:g:~
~~~~
,--
"
,~
.......
I"
,-
~
100
90
zo
'\r--..:,
10
"
....
r,.,
" " " " " U M ~
~
~ T I M (
I/
I
I
-
--~
orl.Ar _.,
,,__
. .
,_
TA&.L
, _ '
TO
10
OESf:l'-T~
~
l' ~
~~
TNC
AIWSTA81.C
N
-
~
,O
:~·r,;-"~~:-1~r:,
S OR
2C:
llfSP£C:T1VII.T
>
AT
2SO\ OF SHOAT
iifl
OCL~T PIC:K•IP "I
~
I
I
.0
.o
Tll€S IROl<ER RATIIIG
-
~
-
"
-
~ ~
---
'
~
~R
~~
~~
.,
I
I
)
4
01
a
lO
tO
50
100
a11
CURRENT
IN
TIMES BREAKER RATING
Fig.
41
(215Dl80) Typical
time-current
characteristics
for Magnet Overcurrent Trip Devices

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents