Peer-To-Peer Interfaces: Enable Transmission And Receipt Of Telegrams; R814 Receive Data On G-Sst3; R815 Transmit Data On G-Sst3 - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
r814
Receive data on G-SST3
When USS protocol (P800=2) is selected:
(G172)
Display of data received via USS interface 3
(G174)
i001:
Display process data word 1
...
i016
Display process data word 16
i017:
Display parameter data word 1
...
i020:
Display parameter data word 4
When peer-to-peer (P800=5) is selected:
Display of data received via peer-to-peer interface 3
i001:
Receive data word 1
...
i005
Receive data word 5
i006:
Not used
...
i020
Not used
r815
Transmit data on G-SST3
When USS protocol (P800=2) is selected:
(G172)
Display of the data to be transmitted via USS interface 3
(G174)
i001:
Display process data word 1
...
i016
Display process data word 16
i017:
Display parameter data word 1
...
i020:
Display parameter data word 4
When peer-to-peer (P800=5) is selected:
Display of the data to be transmitted via peer-to-peer interface 3
i001:
Transmit data word 1
...
i005
Transmit data word 5
i006:
Not used
...
i020
Not used

Peer-to-peer interfaces: Enable transmission and receipt of telegrams:

If transmission on a peer-to-peer interface is disabled, the associated output drivers are connected to high impedance. If reception is
disabled on a peer-to-peer interface, then the telegram failure monitoring function is deactivated.
P816
Peer-to-peer 2: Source for data reception enabling command
0 = binector B0000
(G173)
1 = binector B0001
etc.
P817
Peer-to-peer 2: Source for data transmission enabling command
0 = binector B0000
(G173)
1 = binector B0001
etc.
P818
Peer-to-peer 3: Source for data reception enabling command
0 = binector B0000
(G174)
1 = binector B0001
etc.
P819
Peer-to-peer 3: Source for data transmission enabling command
0 = binector B0000
(G174)
1 = binector B0001
etc.
10-86
Value range
[Unit]
Steps
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 20
P052 = 3
Type: L2
Ind: 20
P052 = 3
Type: L2
Ind: None
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=1
P051 = 40
Type: L2
Offline

Advertisement

Table of Contents
loading

Table of Contents