6.10.1 Configuration display

As shown in Figure 90, highlight the required DC output, then operate the scroll button to reveal the
configuration page.
Select configuration menu
Network
Group
Channel
Virtual Channel
Loop
Digital I/O
DC Output
PARAMETERS
Type
PV
Status
OP Adjust State
Resolution
Output Low
Output High
Scale Low
Scale High
Fallback PV
Measured Value
Note: The output voltage or current can be calibrated by using the output adjust procedure
described in Section 6.1.10.
Page 102
FEC920: USER GUIDE
3A3B (DC.Op)
2A2B (DC.Op)
1A1B (DC.Op)
Figure 90 DC Output option configuration page (typical)
Select V(olts) (3A3B only) or mA as the output type.
Input value to the function. Normally 'wired' to a suitable parameter.
The status of the input parameter.
Adjusted. Appears only if the Output Adjust facility (Section 6.1.10) has been used.
The number of decimal places to be used for this configuration item.
The minimum output value in Volts or mA as appropriate.
The maximum output value to be output in Volts or mA as appropriate.
See 'SCALING INFORMATION' below.
See 'SCALING INFORMATION' below.
The output value when the status of the input parameter is not 'good'.
The Voltage or mA value appearing at the output terminals
A5E45696052A Rev-AA
DC Output.3A3B (DC Op)
Type
V
PV
0.00
Status
Good
OP Adjust State
Adjusted
Resolution
2
Output Low
0.00
Output High
10.00
Scale Low
0.00
Scale High
100.00
Fallback PV
0.00
Measured Value
0.00
Appears only if
the DC Output
has been
adjusted
(Section 6.1.10)