Commissioning
Function staircase lighting after
gateway supply voltage recovery
Options:
This parameter defines if function Staircase lighting is active or inactive after gateway supply voltage re-
covery.
After a gateway supply voltage recovery, the parameterized brightness value in the
Gx
Fault, page 64 is set. The function Staircase lighting is then undertaken with the option defined here.
inactive: The function Staircase lighting is not reactivated after gateway operating voltage recovery.
active: The function Staircase lighting is reactivated after gateway operating voltage recovery. The
lighting group is set using the parameterized basis brightness and can be started by an ON telegram
or renewed activation via the communication object Activate fct. Staircase lighting.
last status: The function Staircase lighting receives the operating state, which it had before gateway
operating voltage failure.
Note
A staircase lighting time in operation before the gateway supply voltage failure is not automatically
restarted. The lighting group is in standby mode with the basis brightness. The function Staircase
lighting will be started only after an ON telegram with the value 1 has been received on the communica-
tion object Switch.
Hinweis
Is a central command e.g. switch, dimming or set brightness received via communication object DALI
output, the staircase function switch in standby and the central command is carried out.
Recall scene
Options:
no reaction
set function in standby
With activated function Staircase lighting, the parameter can be used to define the reaction to a
scene recall.
no reaction: A scene recall is ignored.
set function in standby: A scene telegram ends function Staircase lighting, and the DGN/S car-
ries out the scene recall. The function Staircase lighting is latent and waits until a renewed ac-
tivation via the communication object function Activate fct. Staircase lighting or via an ON tele-
gram to the communication object Switch.
inactive
active
last status
Parameter window –