– The subline length is limited to 3 meters for line topologies
(See section 4.5.2)
– You cannot switch multiple lines in parallel to increase wiring diameter!
∅
A
max. simple line length
[mm
2
]
[mm]
[m]
1,00
1,15
125
0,75
0,98
115
0,50
0,80
75
Address room devices is not supported in the room automation system DESIGO
RXB / RXL (in contrast to DESIGO PX).
Address 1 must, however, be set in the room units (factory setting).
3.1.6
Relay outputs
Fans are controlled using potential-free relay outputs. The following applied for the
wiring:
The maximum load of the relay contracts must be observed (see data sheets for
–
the corresponding controller)
The sizing and fusing of the power lines are oriented to overall connected load
–
and local regulations.
Fusing of switching circuits depends on the controller. The fused electrical
–
values must therefore be reviewed in the data sheets for the corresponding
controllers.
The lines must be fused on the controller with strain relief.
–
Controllers RXB22.1 and RXL22.1 also have a relay contract (Q44) for switching
electrical heating coils. Observe the following:
• The maximum power is 1.8 kW ohm load. Larger loads close the contact too
much.
• A external fuse of max. 10 A is planned to protect room controller circuits.
Installation guide RXB, RXL