Relay Outputs - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

8 / 22
Siemens
Building Technologies
– The subline length is limited to 3 meters for line topologies
(See section 4.5.2)
– You cannot switch multiple lines in parallel to increase wiring diameter!
A
max. simple line length
[mm
2
]
[mm]
[m]
1,00
1,15
125
0,75
0,98
115
0,50
0,80
75
Address room devices is not supported in the room automation system DESIGO
RXB / RXL (in contrast to DESIGO PX).
Address 1 must, however, be set in the room units (factory setting).
3.1.6

Relay outputs

Fans are controlled using potential-free relay outputs. The following applied for the
wiring:
The maximum load of the relay contracts must be observed (see data sheets for
the corresponding controller)
The sizing and fusing of the power lines are oriented to overall connected load
and local regulations.
Fusing of switching circuits depends on the controller. The fused electrical
values must therefore be reviewed in the data sheets for the corresponding
controllers.
The lines must be fused on the controller with strain relief.
Controllers RXB22.1 and RXL22.1 also have a relay contract (Q44) for switching
electrical heating coils. Observe the following:
• The maximum power is 1.8 kW ohm load. Larger loads close the contact too
much.
• A external fuse of max. 10 A is planned to protect room controller circuits.
Installation guide RXB, RXL
Periphery wiring (without bus)
CM110381en_01
28 Feb 2009