Outside air temperature
ETS3 Professional
ACS Service
HandyTool
Parameter outside air supply
Outdoor temp. min. damper pos.
Outside air damper runtime
Min. damper position
106/166
Siemens
Building Technologies
8.6.1

Configuration and parameterization

Basic functions: see sections 8.1.1 through 8.1.7.
The outside temperature is transmitted to the room controller via the KNX bus.
See "Outside air temperature via Konnex bus (FNC10, FNC12, FNC18)", page 80 .
Select Sequences, Other setpoints:
Select Sequences , Other setpoints:
See Parameters in the last column of the table below
Basic
setting
16°C
150s
0%
*)
By temporarily adjusting the setpoint if necessary, the application ensures that
there is a differential of at least 1K between the Outside air temp. min. damper
pos. setpoint and the cooling setpoint of the effective room operating mode.
RXB (KNX) application library
Control sequences
Range
10 °C...40°C *)
0 ... 360s
0 ... 100%
FNC Description of functions for FC-10, FC-11, FC-12
HandyTool
Resolution
parameter
0,5°C
*073
1s
*074
1%
*075