Central Control Of Room Operating Mode Via Input From The Use Timeschedule - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K N X
CO
R
Note
Effective
room operating mode
Switch state
Building in use
Building not in use
Building protection
Siemens
Building Technologies
The state of the room controller (result of the logic OR operation) is mapped to the
building automation and control system via the following S-mode communication object:
Window contact output (Output communication object)
Flags
Type
R W C T U
1 0 1 1 0 1.019
DPT_WindowDoor
Master/slave applications
Bindings are required in S-mode, in order to transmit the slave window contact status to
the master.
5.3.2
Central control of room operating mode via input from
the Use time schedule
Central
Local
Controller
Prio
S
1.
DI
2.
S
3.
S
S
DI
3.
PPS2
3.
S
The table below shows the three possible occupancy states and the resulting e ffective
room operating mode.
Description
• Full availability of all plant
• Building enabled for use
• Inputs of priority 3 are enabled ( Occupancy time
schedule, presence detector, room unit, and
Temporary Comfort mode)
• Reduced availability of plant
• Inputs of priority 3 are disabled ( Occupancy time
schedule, presence detector, room unit, and
Temporary Comfort mode)
• Application:
Building temporarily not in use
The building must reach the Comfort
temperature within hours
• Setpoints reduced to the minimum necessary to
protect the building fabric.
• Inputs of priority 3 are disabled ( Occupancy time
schedule, presence detector, room unit, and
Temporary Comfort mode)
• Application:
Longer periods of non-use of the building
RXB (KNX) application library
Room operating modes
Send heartbeat
Yes
This time schedule determines the overall period of
time for which the entire building is in use. Typically,
this schedule is used for night setback throughout
S
the building, or for longer periods when the building
is not in use.
Outside the "building-in-use" times, inputs from
S
rd
3
priority sources are disabled. This prevents
demand signals from being sent to the primary plant
when, for example, a security guard enters a room.
FNC Description of functions for FC-10, FC-11, FC-12
States
0 = Closed
1 = Open
Effective room op. mode
As defined by Occupancy
time schedule, presence
detector or room unit
Economy
Protection mode
37/166
CM110385en_05
28 Feb 2009