Physical and Operational Specifications

This section provides the physical and operational specifications for the SVi1000. Specifications
are subject to change without notice
Parameter
Operating Temperature Limits
Storage Temperature Limits
Temperature Effect
Supply Pressure Effect
Operating Relative Humidity
Storage Relative Humidity
Humidity Effect
Electromagnetic Compatibility
Electrostatic
Fast Transient Burst
Vibration Influence
Measured at SVi1000 Housing
© 2016 General Electric Company. All rights reserved
Table 6: Environmental Specifications
-40 °F to 185 °F (-40 °C to 85 °C)
-58 °F to 200 °F (-50 °C to 93 °C)
< 0.005% / °F typical; -40 °F to 180 °F (< 0.01% / °C typ-
ical; -40 °C to 82 °C)
0.05% per psi (.73% per bar)
5 to 100% non-condensing
0 to 100% non-condensing
Less than 0.2% after 2 days at 104 °F (40 °C), 95% Rela-
tive Humidity.
IEC 61514 Industrial-Process Control systems - meth-
ods of evaluating the performance of intelligent valve
positioners with pneumatic outputs.
IEC 61326 Electrical equipment for measurement, con-
trol and laboratory use - EMC requirements.
No effect at 2 kV (Coupling clamp EN61000-4-4 or
IEC1000-4-4).
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2% of span
.
Storage & Transport (Packaged)