Step 1: Mounting the SVi1000

This guide provides installation instructions for mounting an SVi1000 on both rotary and recipro-
cating style valves. The mounting process can be broken down into the following:
1. Attach the mounting bracket to the actuator.
2. Install the magnetic assembly.
3. Assemble the SVi1000 on the mounting bracket.
CAUTION
NOTE

Necessary Precautions

To avoid injury or the process being affected when installing or replacing an SVi1000 positioner
on a control valve, ensure that:
For the procedure to install rotary and reciprocating mounting kits on valves, refer to the instruc-
tions contained in the valve's mounting box kit.
© 2016 General Electric Company. All rights reserved
The SVi1000 cover must be in place and secured using all four
screws during operation.
Mount the SVi1000 with the conduit connection down in order to
facilitate drainage of condensate from the conduit.
If the valve is located in a hazardous area, ensure the area has been certified
as safe or that all electrical power to the area has been disconnected before
removing any covers or disconnecting any leads.
Shut off air supply to the actuator and to any valve mounted equipment.
Ensure the valve is isolated from the process by either shutting off the
process or using bypass valves for isolation. Tag shutoff or bypass valves to
guard against a turn-on while work is in progress.
Bleed air from actuator and check that valve is in its unenergized position.
.
Masoneilan SVi1000 Positioner Quick Start Guide =| 23