ABB REC 561 User Manual page 365

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 80
7.2.6 BAYCONF
Apparatus control
Table 11: Input signals for BAYCONF
IN:
BFxx-S_R
BFxx-S_S
BFxx-L_L
BFxx-EXCH_IN
BFxx-RQ_SEL1
BFxx-RQ_SEL2
BFxx-RQ_SEL3
BFxx-RQ_SEL4
BFxx-RQ_SEL5
BFxx-RQ_SEL6
BFxx-RQ_SEL7
BFxx-RQ_SEL8
BFxx-BLK_RE
BFxx-OVERRIDE
BFxx-RE_B1
BFxx-RE_B2
BFxx-RE_B3
BFxx-RE_B4
BFxx-RE_B5
BFxx-RE_B6
BFxx-RE_B7
BFxx-RE_B8
ABB Network Partner AB
DESCRIPTION:
Input to change operator place to Remote
(pulse input)
Input to change operator place to Station
(pulse input)
Input to change operator place to Local
Input for information exchange with other
BAYCON:s in bays with more than 8 appa-
ratuses
Request for selection and reservation of
apparatus 1
Request for selection and reservation of
apparatus 2
Request for selection and reservation of
apparatus 3
Request for selection and reservation of
apparatus 4
Request for selection and reservation of
apparatus 5
Request for selection and reservation of
apparatus 6
Request for selection and reservation of
apparatus 7
Request for selection and reservation of
apparatus 8
Input for blocking all reservations
Input for overriding the reservation function
including the blocking by BLK_RE
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 1
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 2
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 3
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 4
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 5
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 6
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 7
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 8
Version 1.0-00

Hide quick links:

Advertisement

Table of Contents
loading