E3G060 Control module "monitored"
34.1

Overview

34.2
Application
34.3
Key data
Building Technologies
Fire Safety & Security Products
Control module for monitored alarm devices
6 monitored control lines 24 V, 2 A with EMI and over voltage protection
Individual allocation of control lines via maintenance PC (AlgoWorks)
It is possible to specify separately whether or not each line must be activated in
"Emergency alarm" mode
Card format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
the E3G060 module is required in systems with more than 2 monitored control
lines for alarm / or similar equipment
the current on one control line may not exceed 2 A; however, the total current for
all 6 control lines may not exceed 4 A
Control outputs
number
max. load
termination resistor
Quiescent current at 24 V
Terminal block X1 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
E3G060 Control module "monitored" (Part No 460514)
6
2 A each at 24...29.6 V
4.75 kΩ
25 mA (no control line active)
(Part No 460514)