Current Consumption - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

27.5

Current consumption

27.6
Connections
E3M220
Line termination Pos V31
Line 1
Transzorb 20V
Line termination Pos V33
Line 2
Transzorb 20V
Line 1 / MS5
Line 2 / MS5
Plug-in terminals
Input Supply
Building Technologies
Fire Safety & Security Products
4
Glow lamp "H9" (65 V, 1.5 mA): 220 V ON
5
Plug-in terminals "K1": Module supply 24 V
6
4-pin female connector strip with connection cable
7
Fuse: 'F1' 1 A/F
24 V
Quiescent
condition
Alarm status
max.
X10
Terminal block
+
1
-
2
+
3
-
4
5
+
6
-
7
+
8
-
9
10
11
12
13
14
15
16
17
18
19
20
K1
-
1
0V
-
2
3
F1
+
4
Module supply (SMD fuse can only be changed at factory)
both lines with 150 kΩ end-of-line resistor
both lines with 82 kΩ end-of-line resistor
both lines short circuit
to E3M080
Please note:
- Exchange existing (82k ) end -of-line resistors for 150k end-of-line
resistors, in order to reduce the quiescent current
- Manual call points require a 10k /2
- Line resistor up to 250
-
24V
+
E3M220 MS5 Adapter
227 mA
247 mA
+ 120 mA per line Alarm status
695 mA
End-of-line resistor 82 ... 150kΩ
End-of-line resistor 82 ... 150kΩ
Ω Ω
resistor, in order to activate alarm
001260_k_en_--.doc
113
02.2005