Control Systems
Building management system
VI
VI
2. DMS B-net (BACnet GW)
MIM-B17N
7) Object list
(2) AHU kit
Single AHU unit has following point list.
Instance
Number
1
Indoor Temperature
2
Set temperature
3
Setting lower temperature limit
4
Setting upper temperature limit
The power value of an indoor
5
unit after the basic date
The number of hours usage of an
6
indoor unit after the basic date
7
Power value within period
The number of hours usage of
8
an indoor unit within period
9
Power On/Off
Applying lower temperature
limit setting
Applying upper temperature
11
limit setting
12
Filter sign status
13
Filter sign reset
14
Operation mode status
15
Operation mode limit status
16
Remote controller limit status
Integrated error code of both
17
indoor unit and outdoor unit
Discharge cooling set
( )
18
temperature
Discharge heating set
( )
19
temperature
Discharge current
( )
temperature
( )
21
Humidification setting
( )
22
Outdoor air intake setting
( )
23
Outdoor cooling setting
( )
24
Fan speed status
( )
25
Set humidity status
( )
26
Current humidity status
27
AHU Notify
( )
Mark is optionally supported.
168
Object
Object
Type
AI
AHU_RoomTemp_xx_xxxxxx
AV
AHU_Temp_Set_xx_xxxxxx
AV
AHU_Cool_LimitTemp_xx_xxxxxx
AV
AHU_Heat_LimitTemp_xx_xxxxxx
AI
AHU_Baseline_kWh_xx_xxxxxx
AI
AHU_Baseline_Minute_xx_xxxxxx
AI
AI
BV
BV
AHU_Cool_Limit_set_xx_xxxxxx
BV
AHU_Heat_Limit_set_xx_xxxxxx
BI
AHU_FilterSign_xx_xxxxxx
BO
AHU_FilterSign_Reset_xx_xxxxxx
MV
AHU_Operation_Mode_xx_xxxxxx
MV
AHU_Mode_Limit_xx_xxxxxx
MV
AHU_Remocon_Limit_xx_xxxxxx
AI
AHU_Error_Code_xx_xxxxxx
AV
AHU_DisCoolSetTemp_xx_xxxxxx
AV
AHU_DisHeatSetTemp_xx_xxxxxx
AI
AHU_Dis_CurrentTemp_xx_xxxxxx
BV
AHU_Humidification_xx_xxxxxx
BV
AHU_OAIntake_xx_xxxxxx
BV
AHU_OutdoorCool_xx_xxxxxx
MV
AHU_FanSpeed_xx_xxxxxx
MV
AHU_SetHumidity_xx_xxxxxx
MI
AHU_CurrentHumidity_xx_xxxxxx
NC
AHU_Notify_xx_xxxxxx
Unit
Object Name
Inactive
Text-1
kWh
Minute
kWh
Minute
Off
False
False
False
False
Auto
No
Limit
Enable
RC
Refer to Samsung integrated error code list
°C
°C
°C
Off
Off
Off
Low
Low
Low
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Status value
Active
Text-2
Text-3
Text-4
Text-5
On
True
True
True
True
Cool
Heat
Fan
Dry
Cool
Heat
Only
Only
Disable
Conditional
RC
RC
On
On
On
Mid
High
Mid
High
Mid
High

Hide quick links: