Remote Thermostats - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
®
25
Fan level manual control 3
This 1-bit communication object can be used to send an ON telegram, if the second fan stage
to be switched on. An OFF telegram is sent, if the third fan stage is no longer to be switched on.
This data item forms the 1-bit KNX object and can be sent and received.
36
Speed 1 automatic control
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
37
Speed 2 automatic control
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
38
Speed 3 automatic control
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
6.3.5

Remote thermostats

No.
Function
39,40,
Remote mode 1,2,3
41
It sends the set operating mode of the Programmable Thermostat to the possible three remote thermostats. The
possible values are:
0: Programmable Thermostat mode
1: Programmable Thermostat setpoint only
2: Setpoint + comfort mode
42,43,
Remote setpoint 1,2,3
44
It sends the setpoint temperature value of the Programmable Thermostat to the remote thermostats.
Commissioning
Manual fan
1 bit EIS1 DPT 1.001
Automatic fan
1 bit EIS1 DPT 1.003
Automatic fan
1 bit EIS1 DPT 1.003
Automatic fan
1 bit EIS1 DPT 1.003
Object name
Remote
thermostats
Remote
thermostats
Type of datum
1 byte EIS1 DPT
20.102
2 byte EIS1 DPT 9.001
MYLOS
Building Automation | Commissioning 61
®
C,R,W,T
C,R,W,T,U
C,R,W,T,U
C,R,W,T,U
Flags
C,R,T
C,R,T