6.3

Communication objects

6.3.1

General

No.
Function
0
In operation
Sends the object value „0" or „1" to the bus cyclically. Object value and cycle time can be set
in the parameters.
The telegram can be used for monitoring the device operation, e.g. by a monitoring block.
19
Device On / Off
The controller is activated via this 1-bit communication object when an ON telegram is received and deactivated
when an OFF telegram is received. It can receive and send. Switching the controller on and off is the same as
actuating the ON/OFF switch on the device.
When the device is switched off OFF is shown on the display, but the controller setpoint is switched to a
parametrisable temperature setpoint and the fan switches off immediately.
0: switch off device or device is switched off
1: switch on device or device is switched on
54 Commissioning | MYLOS
Building Automation
®
Commissioning
Object name
Type of datum
General
1 bit EIS1 DPT 1.001
General
1 bit EIS1 DPT 1.001
Flags
C,T
C,R,W,T