☞ The controller does not communicate with the Host-PC.
Cause
A defective cable is used, errors in wiring, an error in setting COMM ID of the controller, or damage on
the communication port (either on PC side or on the controller side).
Solution
1. Please check the settings of the application S/W and the controller.
- Check if the controller's COMM ID is listed on the application S/W.
- Set the different COMM ID when two or more co
- Check if the communication speed (9600bps def
- Make sure that the PC's COM port is set correctly on the S/W.
- The parameters at the S/W should be set as following:
Parity bit
Data bit
Stop bit
2. Check the line connection for communication.
3. In case of setting RS485 communication, we recommend to use line-end resistors of 120 Ohm
between the RTX (+) and RTX (-) lines. Apply the same resistors to the converter RS485 lines.
Consult a service center or an electric technician if you are no
4. When a multi-drop communication doesn't work, test one
5. If the trouble remains after the procedure above, contact a
: NONE
: 8bit
: 1bit
RS232
GE313
PC
RX
TX
TX
RX
GND
GND
GE314
GE314
RX(-)
RX(-)
RX(+)
RX(+)
ntrollers are installed
ault) is the same as the setting on the S/W.
RS485 (mono)
RS485/232
GE314
Converter
RTX(-)
RTX(-)
RTX(+)
RTX(+)
RS485(Multi Drop)
RS485/232
Converter
The RS232 cable from
TX(-)
the converter
TX(+)
66
.
PC
The RS232 cable from
the converter
PC
t sure how to do it.
-by-one communication first.
designated service center.