GE L30 Instruction Manual page 499

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 49 of 52)
ADDR
REGISTER NAME
D3D4
...Repeated for Remote Device 22
D3D8
...Repeated for Remote Device 23
D3DC
...Repeated for Remote Device 24
D3E0
...Repeated for Remote Device 25
D3E4
...Repeated for Remote Device 26
D3E8
...Repeated for Remote Device 27
D3EC
...Repeated for Remote Device 28
D3F0
...Repeated for Remote Device 29
D3F4
...Repeated for Remote Device 30
D3F8
...Repeated for Remote Device 31
D3FC
...Repeated for Remote Device 32
Phasor Measurement Unit Communication (Read/Write Setting)
D400
PMU 1 Communication Port 1 Type
D401
PMU 1 Communication Port 2 Type
D402
PMU 1 Communication Port 3 Type
D403
PMU 1 Port 1 PHS-x (14 items)
D411
PMU 1 Port 2 PHS-x (14 items)
D41F
PMU 1 Port 3 PHS-x (14 items)
D42D
PMU 1 Communication Port 1 PHS-x Name (14 items)
D49D
PMU 1 Port 2 PHS-x Name (14 items)
D50D
PMU 1 Port 3 PHS-x Name (14 items)
D57D
PMU 1 Port 1 A-CH-x (8 items)
D585
PMU 1 Port 2 A-CH-x (8 items)
D58D
PMU 1 Port 3 A-CH-x (8 items)
D595
PMU 1 Port 1 A-CH-x Name (8 items)
D5D5
PMU 1 Port 2 A-CH-x Name (8 items)
D615
PMU 1 Port 3 A-CH-x Name (8 items)
D655
PMU 1 Port 1 D-CH-x (16 items)
D665
PMU 1 Port 2 D-CH-x (16 items)
D675
PMU 1 Port 3 D-CH-x (16 items)
D685
PMU 1 Port 1 D-CH-x Name (16 items)
D705
PMU 1 Port 2 D-CH-x Name (16 items)
D785
PMU 1 Port 3 D-CH-x Name (16 items)
D705
PMU 1 Port 1 D-CH-x Normal State (16 items)
D715
PMU 1 Port 2 D-CH-x Normal State (16 items)
D725
PMU 1 Port 3 D-CH-x Normal State (16 items)
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4
PMU 1 Recording Clear Command
E4D5
PMU 1 Recording Force Trigger
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC
PMU 1 Recording Rate
E4DD
Reserved
E4DE
PMU 1 No Of Timed Records
E4DF
PMU 1 Trigger Mode
E4E0
PMU 1 Timed Trigger Position
E4E1
Reserved
E4E2
PMU 1 Record PHS-1 (14 items)
E4F0
PMU 1 Record PHS-x Name (14 items)
E560
PMU 1 Record A-CH-x (8 items)
E568
PMU 1 Record A-CH-x Name (8 items)
E5A8
PMU 1 Record D-CH-x (16 items)
E5B8
PMU 1 Record D-CH-x Name (16 items)
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
EA4C
PMU Network Reporting Function
GE Multilin
RANGE
0 to 3
0 to 3
0 to 3
0 to 14
0 to 14
0 to 14
---
---
---
0 to 65535
0 to 65535
0 to 65535
---
---
---
0 to 65535
0 to 65535
0 to 65535
---
---
---
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 10
---
1 to 128
0 to 1
1 to 50
---
0 to 14
---
0 to 65535
---
0 to 65535
---
0 to 1
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F545
---
1
F545
---
1
F545
---
1
F543
---
1
F543
---
1
F543
---
---
F203
"GE-UR-PMU-PHS 1"
---
---
F203
"GE-UR-PMU-PHS 1"
---
---
F203
"GE-UR-PMU-PHS 1"
---
1
F600
---
1
F600
---
1
F600
---
---
F203
"AnalogChannel 1"
---
---
F203
"AnalogChannel 1"
---
---
F203
"AnalogChannel 1"
---
1
F300
---
1
F300
---
1
F300
---
---
F203
---
---
F203
---
---
F203
---
1
F108
---
1
F108
---
1
F108
---
1
F126
---
1
F126
---
1
F544
---
1
F001
---
1
F001
---
1
F542
0 (Auto Overwrite)
%
1
F001
---
1
F001
---
1
F543
---
---
F203
GE-UR-PMU-PHS 1
---
1
F600
---
---
F203
AnalogChannel 1
---
1
F300
---
---
F203
---
1
F102
DEFAULT
B
0 (Network)
0 (Network)
0 (Network)
1 (Va)
1 (Va)
1 (Va)
0
0
0
0
0
0
"Dig Channel 1"
"Dig Channel 1"
"Dig Channel 1"
0 (Off)
0 (Off)
0 (Off)
0 (No)
0 (No)
3 (10/sec.)
0
3
10
0
1 (Va)
0
0
Dig Channel 1
0 (Disabled)
B-57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents