B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 52)
ADDR
REGISTER NAME
5E02
Ground Instantaneous Overcurrent 1 Pickup
5E03
Ground Instantaneous Overcurrent 1 Delay
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
5E05
Ground Instantaneous Overcurrent 1 Block
5E06
Ground Instantaneous Overcurrent 1 Target
B
5E07
Ground Instantaneous Overcurrent 1 Events
5E08
Reserved (8 items)
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
5F11
Stub Bus Disconnect
5F12
Stub Bus Trigger
5F13
Stub Bus Target
5F14
Stub Bus Events
50DD Disturbance Detection (Read/Write Grouped Setting)
5F20
50DD Function
5F21
50DD Non Current Supervision
5F22
50DD Control Logic
5F23
50DD Logic Seal In
5F24
50DD Events
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
5F89
Setting Group Function
5F8A
Setting Group Events
Setting Groups (Read Only)
5F8B
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Current Differential 87L (Read/Write Grouped Setting)
6000
87L Current Differential Function
6001
87L Current Differential Block
6002
87L Current Differential Signal Source 1
6003
87L Minimum Phase Current Sensitivity
6004
87L Current Differential Tap Setting
6005
87L Current Differential Phase Percent Restraint 1
6006
87L Current Differential Phase Percent Restraint 2
6007
87L Current Differential Phase Dual Slope Breakpoint
B-30
RANGE
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 65535
---
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 65535
0 to 5
0.1 to 4
0.2 to 5
1 to 50
1 to 70
0 to 20
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
---
0.01
F001
%
1
F001
%
1
F001
pu
0.1
F001
DEFAULT
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
0
0 (SRC 1)
20
100
30
50
10
GE Multilin