220 Parameters
No.
Name/Value
14.79
AO1 filter time
0.000 ... 30.000 s
Description
(Visible when
14.01 Module 1 type
Defines the filtering time constant for analog output AO1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Filter time constant.
=
FIO-11
or FAIO-01)
t
)
Def/FbEq16
0.100 s
1000 = 1 s