Advanced Videographic Recorder
SM2000
•1 If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.
IM/SM2000
Issue 11
Set the required electrical range.
Notes.
Applicable only to mA, mV, V and Resistance input types.
When an input is connected through an external voltage
divider (see
Warnings
low and high values to the actual voltage applied to the
divider, not the voltage after it has been divided down. The
range of the electrical input signal is determined by the
input type – see Table 4.3:
Input
Standard Inputs
Type
mV
V
mA
Min.
0
0
Max.
2000
20
Table 4.3 Limits of Electrical Ranges
Specify the display range and units of the engineering value
•1
corresponding to the electrical high and low values, within the
limits defined in Table 4.4:
THC/RTD
Type
Type B
Type E
Type J
Type K
Type L
Type N
Type R & S
Type T
Pt100
Power 5/2
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 4.4 Limits of Engineering Ranges
Example – for an electrical input range of 4.0 to 20.0mA,
representing a pressure range of 50 to 250 bar, set the 'Low'
value to 50.0 and the 'High' value to 250.0.
4 CONFIGURATION
on page 80), set the electrical range
High Specification Inputs
mV
V
0
0
–1000
–50
–100
50
5000
1000
50
100
°C
Min.
Max.
Min.
–18
1800
0
–100
900
–140
–100
900
–140
–100
1300
–140
–100
900
–140
–200
1300
–325
–18
1700
0
–250
300
–400
–200
600
–325
–999 to +9999
mA
0
2000
°F
Max.
3270
1650
1650
2350
1650
2350
3090
570
1100
81