B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 30 of 59)
ADDR
REGISTER NAME
7080
Phase Distance Zone 1 Quad Left Blinder RCA
7081
Phase Distance Zone 1 Volt Limit
7082
Phase Distance Zone 1 Transformer Voltage Connection
7083
Phase Distance Zone 1 Transformer Current Connection
7084
Phase Distance Zone 1 Rev Reach
B
7085
Phase Distance Zone 1 Rev Reach RCA
7086
Reserved (10 items)
7090
...Repeated for Phase Distance Zone 2
70B0
...Repeated for Phase Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71F0
Line Pickup Function
71F1
Line Pickup Signal Source
71F2
Line Pickup Phase IOC Pickup
71F3
Line Pickup UV Pickup
71F4
Line End Open Pickup Delay
71F5
Line End Open Reset Delay
71F6
Line Pickup OV Pickup Delay
71F7
Autoreclose Coordination Pickup Delay
71F8
Autoreclose Coordination Reset Delay
71F9
Autoreclose Coordination Bypass
71FA
Line Pickup Block
71FB
Line Pickup Target
71FC
Line Pickup Events
71FD
Terminal Open
71FE
Autoreclose Accelerate
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
7261
Phase Directional Overcurrent 1 Source
7262
Phase Directional Overcurrent 1 Block
7263
Phase Directional Overcurrent 1 ECA
7264
Phase Directional Overcurrent 1 Pol V Threshold
7265
Phase Directional Overcurrent 1 Block Overcurrent
7266
Phase Directional Overcurrent 1 Target
7267
Phase Directional Overcurrent 1 Events
7268
Reserved (8 items)
7270
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
7281
Neutral Directional Overcurrent 1 Source
7282
Neutral Directional Overcurrent 1 Polarizing
7283
Neutral Directional Overcurrent 1 Forward ECA
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
7285
Neutral Directional Overcurrent 1 Forward Pickup
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
7287
Neutral Directional Overcurrent 1 Reverse Pickup
7288
Neutral Directional Overcurrent 1 Target
7289
Neutral Directional Overcurrent 1 Block
728A
Neutral Directional Overcurrent 1 Events
728B
Neutral Directional Overcurrent 1 Polarizing Voltage
728C
Neutral Directional Overcurrent 1 Op Current
728D
Neutral Directional Overcurrent 1 Offset
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
728F
Reserved
7290
...Repeated for Neutral Directional Overcurrent 2
B-38
RANGE
60 to 90
0 to 5
0 to 12
0 to 12
0.02 to 500
30 to 90
---
0 to 1
0 to 5
0 to 30
0 to 3
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 2
-90 to 90
40 to 90
0.002 to 30
40 to 90
0.002 to 30
0 to 2
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 250
0 to 0.5
0 to 1
L90 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
degrees
1
F001
pu
0.001
F001
---
1
F153
---
1
F153
ohms
0.01
F001
degrees
1
F001
---
---
F001
---
1
F102
---
1
F167
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F102
---
1
F167
---
1
F300
---
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F230
° Lag
1
F002
degrees
1
F001
pu
0.001
F001
degrees
1
F001
pu
0.001
F001
---
1
F109
---
1
F300
---
1
F102
---
1
F231
---
1
F196
ohms
0.01
F001
---
0.001
F001
---
1
F001
DEFAULT
85
0
0 (None)
0 (None)
200
85
0
0 (Disabled)
0 (SRC 1)
1000
700
150
90
40
45
5
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Voltage)
75
90
50
90
50
0 (Self-reset)
0
0 (Disabled)
0 (Calculated V0)
0 (Calculated 3I0)
0
63
0