GE L90 Instruction Manual page 607

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 59)
ADDR
REGISTER NAME
68AD
Autoreclose 1P Dead Time
68AE
Autoreclose Breaker Sequence
68AF
Autoreclose Transfer Time
68B0
Autoreclose Event
68B1
Autoreclose 3P Dead Time 3
68B2
Autoreclose 3P Dead Time 4
68B3
Autoreclose Bus Fault Initiate
68B4
Autoreclose Initiate Mode
68B5
Reserved (11 items)
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7007
Phase Undervoltage 1 Target
7008
Phase Undervoltage 1 Events
7009
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7046
Phase Overvoltage 1 Target
7047
Phase Overvoltage 1 Events
7048
Reserved (8 items)
Distance (Read/Write Grouped Setting)
7060
Distance Signal Source
7061
Memory Duration
7062
Force Self-Polarization
7062
Force Memory Polarization
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070
Phase Distance Zone 1 Function
7071
Phase Distance Zone 1 Current Supervision
7072
Phase Distance Zone 1 Reach
7073
Phase Distance Zone 1 Direction
7074
Phase Distance Zone 1 Comparator Limit
7075
Phase Distance Zone 1 Delay
7076
Phase Distance Zone 1 Block
7077
Phase Distance Zone 1 Target
7078
Phase Distance Zone 1 Events
7079
Phase Distance Zone 1 Shape
707A
Phase Distance Zone 1 RCA
707B
Phase Distance Zone 1 DIR RCA
707C
Phase Distance Zone 1 DIR Comp Limit
707D
Phase Distance Zone 1 Quad Right Blinder
707E
Phase Distance Zone 1 Quad Right Blinder RCA
707F
Phase Distance Zone 1 Quad Left Blinder
GE Multilin
RANGE
0 to 655.35
0 to 4
0 to 655.35
0 to 1
0 to 655.35
0 to 655.35
0 to 65535
0 to 1
---
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
5 to 25
0 to 65535
0 to 65535
0 to 1
0.05 to 30
0.02 to 500
0 to 2
30 to 90
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 1
30 to 90
30 to 90
30 to 90
0.02 to 500
60 to 90
0.02 to 500
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.01
F001
---
1
F082
s
0.01
F001
---
1
F102
s
0.01
F001
s
0.01
F001
s
0.01
F300
---
1
F610
0 (Protection AND CB)
---
---
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
0 (Phase to Ground)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F167
cycles
1
F001
---
1
F300
---
1
F300
---
1
F102
pu
0.001
F001
ohms
0.01
F001
---
1
F154
degrees
1
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F120
degrees
1
F001
degrees
1
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
DEFAULT
100
3 (1 - 2)
400
0 (Disabled)
200
B
400
0
0
0 (Disabled)
0 (SRC 1)
1000
0 (Definite Time)
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (SRC 1)
10
0
0
0 (Disabled)
200
200
0 (Forward)
90
0
0
0 (Self-reset)
0 (Disabled)
0 (Mho)
85
85
90
1000
85
1000
B-37