GE L90 Instruction Manual page 603

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 59)
ADDR
REGISTER NAME
Wattmetric ground fault settings (read/write grouped, 2 modules)
B300
Wattmetric ground fault 1 function
B301
Wattmetric ground fault 1 source
B302
Wattmetric ground fault 1 voltage
B303
Wattmetric ground fault 1 overvoltage pickup
B304
Wattmetric ground fault 1 current
B305
Wattmetric ground fault 1 overcurrent pickup
B306
Wattmetric ground fault 1 overcurrent pickup delay
B307
Wattmetric ground fault 1 power pickup
B308
Wattmetric ground fault 1 ECA
B309
Wattmetric ground fault 1 power pickup delay
B30A
Wattmetric ground fault 1 curve
B30B
Wattmetric ground fault 1 multiplier
B30C
Wattmetric ground fault 1 block
B30D
Wattmetric ground fault 1 target
B30E
Wattmetric ground fault 1 events
B30F
Wattmetric ground fault 1 reference power
B310
Wattmetric ground fault x Reserved
6061
...Repeated for wattmetric ground fault 2
Wattmetric ground fault actual values (read only)
B360
Wattmetric ground fault 1 operating power
6074
Wattmetric ground fault 2 operating power
CT Failure Detector (Read/Write Setting)
6124
CT Fail Function
6125
CT Fail Block
6126
CT Fail Current Source 1
6127
CT Fail Current Pickup 1
6128
CT Fail Current Source 2
6129
CT Fail Current Pickup 2
612A
CT Fail Voltage Source
612B
CT Fail Voltage Pickup
612C
CT Fail Pickup Delay
612D
CT Fail Target
612E
CT Fail Events
Continuous Monitor (Read/Write Setting)
6130
Continuous Monitor Function
6131
Continuous Monitor I OP
6132
Continuous Monitor I Supervision
6133
Continuous Monitor V OP
6134
Continuous Monitor V Supervision
6135
Continuous Monitor Target
6136
Continuous Monitor Events
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
6301
Negative Sequence Time Overcurrent 1 Signal Source
6302
Negative Sequence Time Overcurrent 1 Pickup
6303
Negative Sequence Time Overcurrent 1 Curve
6304
Negative Sequence Time Overcurrent 1 Multiplier
6305
Negative Sequence Time Overcurrent 1 Reset
6306
Negative Sequence Time Overcurrent 1 Block
6307
Negative Sequence Time Overcurrent 1 Target
6308
Negative Sequence Time Overcurrent 1 Events
6309
Reserved (7 items)
6310
...Repeated for Negative Sequence Time Overcurrent 2
GE Multilin
RANGE
0 to 1
0 to 5
0 to 1
0.02 to 3.00
0 to 1
0.002 to 30.000
0 to 600
0.001 to 1.2
0 to 360
0 to 600
0 to 5
0.01 to 2
0 to 65535
0 to 2
0 to 1
0.001 to 1.2
0 to 1
0 to 999999.999
0.000 to 1000000.000
0 to 1
0 to 65535
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
0 to 30
0 to 16
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
---
1
F234
0 (Calculated VN)
pu
0.01
F001
---
1
F235
pu
0.001
F001
s
0.01
F001
pu
0.001
F001
° Lag
1
F001
s
0.01
F001
---
1
F236
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
pu
0.001
F001
---
1
F001
W
0.001
F060
W
0.001
F060
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
20
B
(Calculated IN)
60
20
100
0
20
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
500
0
0
0
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
1000
100
0
0 (Self-reset)
0 (Disabled)
0
B-33