SmartLogger2000-(10-C, 11-C)
User Manual
No
Paramet
Function
.
er
17
Compens
Specifies the
ation
compensation
offset
offset voltage
voltage
between PV and
PE after the PID
module operates
stably.
18
Clear
Clears the active
Data
alarms and
historical alarms
stored on the PID
module.
7.7.8 Custom Device
The SmartLogger can connect to third-party devices supporting the Modbus-RTU protocol,
such as the box-type transformer and EMI. Since the protocol specifications vary depending
on vendors, you need to obtain a protocol specifications file in .cfg format from Huawei and
import the file into the SmartLogger for successfully connecting to a third-party device.
7.7.8.1 Querying Related Information
Select a custom device on the Monitoring page and query its information on the displayed
page.
Issue Draft A (2017-02-15)
Value
0–500 V
N/A
Custom devices cannot be detected automatically and need to be added manually. For details, see
7.10.7.1 Connecting
Devices.
The SmartLogger can connect to a maximum of five types of custom devices and can connect to
multiple devices of the same type.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Description
If PV module compensation voltage direction is set
to PV– positive offset, this parameter specifies the
positive voltage between PV– and the ground.
If PV module compensation voltage direction is set
to PV+ positive offset, this parameter specifies the
negative voltage between PV+ and the ground.
NOTE
If Compensation offset voltage i set to 500 V, the PID module
provides the maximum output to enhance the voltage
compensation effect. The output voltage amplitude of the PID
module is automatically capped to ensure the safety of a PV
power plant. The output voltage amplitude is also related to the
maximum system DC-to-ground withstand voltage and maximum
output voltage.
You can select Clear Data to clear active alarms and
historical alarms for the PID module.
7 WebUI