Step 3: Basic Configuration
This section serves as an example where the AO block and TB block are configured. However,
there are a number of combinations that can be configured. This discussion is valid if the posi-
tioner is controlled by the AO block.
1. For the Transducer block set:
See Transducer Block Parameters in the SVI FF instruction manual for further
settings.
2. For the AO block review/set as below:
© 2017 General Electric Company. All rights reserved
ACTUATOR_3.ACT_FAIL_ACTION_1 = either 1. Valve Closed (most common) or
2. Valve Open
ACCESSORY.REMOTE_SENSOR = 0, if remote sensor is not in use (internal
Hall sensor is used)
ACTIVATE_CONTROL_SET to one of:
0: Activate Custom
Control Set
(required for Auto-
tune as well - most
common)
3: Activate Control
Set 3
6: Activate Control
Set 6 (Double Acting
- Slow)
CHAR_SELECTION.TYPE to one of:
0. Linear (most
common)
3. Quick Open
(reversal from Equal
Percentage (50:1))
PV_SCALE.UNIT
INDEX = %
SHED_OPT =
NORMAL SHED
NORMAL RETURN
1: Activate Control
Set 1 (Slowest)
4: Activate Control
Set 4
7: Activate Control
Set 7 (Double
Acting- Fast)
1. Equal Percent-
age (30:1)
4. Custom
XD_SCALE.UNIT
INDEX = %
.
Masoneilan SVI FF Positioner Quick Start Guide =| 15
2: Activate Control
Set 2
5: Activate Control
Set 5 (Fastest)
2. Equal Percent-
age (50:1)
5. Camflex
Percentage
CHANNEL = Position