ANNUNCIATOR PANEL
506
Figure 428: Typical annunciator display
There are three control buttons at the bottom of the display.
The Next Page button cycles through the pages of alarms and to the self-test page.
The Next Alarm button cycles horizontally through the current alarms, from left to
right, starting with the first row of alarms. A graphical frame borders the current
status box to indicate the selected alarm. The front panel display is dynamically
controlled according to the selected alarm.
The Ack button controls the state of the alarms.
The annunciator alarm sequence conforms to ISA 18.1-1979 (R1992) standard, type R.
Figure 429: Annunciator alarm sequence
The annunciator states are described in the following table.
Table 44: Annunciator states
Line
Process
1
Normal
2
Abnormal
3A
Abnormal
3B
Normal
4
Normal
5
Abnormal
6
Normal
The visual indications are displayed as follows.
Off: grey text on a darker grey background.
On: bright white text on a colored background.
Fast flash: Alternating between the off state and the on state two times per second.
Slow flash. Alternating between the off state and the on state one time per second
In the event of an alarm, the page containing the alarm will be promoted to active page. If
there are multiple pages with alarms, the page with the lowest page number is promoted.
Pushbutton
---
---
Acknowledge
Acknowledge
---
---
Reset
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 12: LOCAL INTERFACE
Sequence
Visual indication
Normal
Off
Alarm
Fast flash
Acknowledged
On
To line 4
To line 4
Ringback
Slow flash
To line 2
To line 2
Normal
Off

Advertisement