IEC 61850 COMMUNICATIONS
Configurable GOOSE reception
106
ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
ConfRev
Range: 0 to 16383 in steps of 1
Default: 0
This value changes automatically as described in IEC 61850 part 7-2.
Dataset Item 1, Dataset Item 2, Dataset Item 3,..., Dataset Item 64
Range: all valid MMS data item references for transmitted data
Default: 0
These settings are used to select an MMS data item for each configurable GOOSE
dataset item.
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status
indication and its associated quality flags, the following dataset items can be selected:
"GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The D90
containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined
by the operand assigned to GGIO1 indication 1. Changes to this operand will result in the
transmission of GOOSE messages containing the defined dataset.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Reception > Rx Configurable GOOSE menu item to open the configurable GOOSE
reception configuration window.
Figure 81: Configurable GOOSE reception configuration settings
The following settings are available for each dataset for configurable GOOSE reception.