LOGIC DIAGRAMS
4
4-30
Figure 4-24: Logic diagram
SETTINGS
TRIP BUS 1 INPUT 1
= Off
TRIP BUS 1 INPUT 2
= Off
OR
TRIP BUS 1 INPUT 16
= Off
SETTINGS
TRIP BUS 1
FUNCTION
= Enabled
TRIP BUS 1 BLOCK
AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP
SETTINGS
TRIP BUS 1 PICKUP
DELAY
Non-volatile,
TRIP BUS 1 RESET
set-dominant
DELAY
AND
S
T
PKP
Latch
R
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
FLEXLOGIC OPERAND
TRIP BUS 1 OP
T
RST
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
842023A1.CDR