GE 239 Instruction Manual page 83

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

5 MONITORING
SEE PREVIOUS PAGE
] LAST TRIP DATA
]
MESSAGE
MESSAGE
] MOTOR STATISTICS
]
] SWITCH STATUS
]
MESSAGE
MESSAGE
SEE NEXT PAGE
GE Multilin
Courtesy of NationalSwitchgear.com
4
MESSAGE
CAUSE OF LAST TRIP:
NO TRIP
3
A=
0 B=
MESSAGE
C=
0 AMPS
GROUND CURRENT=
0.0 A
CURRENT UNBALANCE
U/B= 0%
STATOR RTD 1 TEMP:
130°C
BEARING RTD 2
NO RTD
BEARING RTD 3
NO RTD
SETPOINTS GROUP
IN USE: MAIN
2nd LAST TRIP:
NO TRIP
4
MESSAGE
MOTOR MAX STARTING
CURRENT = 0 A
3
RUNNING TIME:
MESSAGE
0.0 h
4
MESSAGE
SW. 1 ACCESS
SWITCH STATE: OPEN
3
SW.2 EMERG RESTART
MESSAGE
SWITCH STATE: OPEN
SW.3 EXTERNAL RESET
SWITCH STATE: OPEN
OPTION SWITCH 1
SWITCH STATE: OPEN
OPTION SWITCH 2
SWITCH STATE: OPEN
MAIN SETPOINTS GROUP
CURRENTLY IN USE
239 Motor Protection Relay
Range: NO TRIP, OVERLOAD, SHORT CIRCUIT, MECHANICAL
JAM, UNBALANCE, GROUND FAULT, STATOR RTD, BEARING
RTD, UNDERCURRENT, THERMISTOR, COMPUTER TRIP,
PARAMETERS NOT SET, OPTION SWITCH 1, OPTION SWITCH 2
Range: 0 to 10000
0
Range: 0 to 1000
Range: 0 to 100
Range: –40 to +200 °C
–40 to +400 °F
Range: –40 to +200 °C
–40 to +400 °F
Range: –40 to +200 °C
Range: MAIN, 2nd, 3rd, 4th
3rd LAST TRIP:
NO TRIP
4th LAST TRIP:
NO TRIP
5th LAST TRIP:
NO TRIP
Range: 0 to 10000 A
Range: 0 to 429496729.6 hrs
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
5 MONITORING
–40 to +400 °F
Range: Same as CAUSE OF
LAST TRIP above
5-3
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents