GE 239 Instruction Manual page 27

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

2 INSTALLATION
h) ANALOG OUTPUT (OPTION) (18/19/20)
Terminals 18-20 of the 239 are available for a single analog current output of one parameter. Verify
that the Analog Output option is installed by noting that the product identification label on back of the
relay includes -AN in the order code. The choice of output and current range is selected in 6
6(783?$1$/2* 287387?$1$/2* 287387 7<3(
lowing for output: phase CT (secondary) amps, % motor full load current (FLC), thermal capacity
used (100% = motor tripped), RTD1 temperature, RTD2 temperature, or RTD3 temperature. The
RANGE message selects the output current as: 0-1 mA, 0-20 mA or 4-20 mA. Range assignment is
shown below in Table 2–4: ANALOG OUTPUT RANGE ASSIGNMENT.
Table 2–4: ANALOG OUTPUT RANGE ASSIGNMENT
SELECTED OUTPUT
Average Phase Current
Motor Full Load %
Thermal Capacity
RTD 1-3 Temperature
Forced Output
* 1 Amp CT secondary = 1 A, 5 Amp CT secondary = 5 A
This output is a current source suitable for connection to a remote meter, chart recorder, programma-
ble controller, or computer load. Use the 4-20 mA with a programmable controller that has a current
input. If only a voltage input is available use a scaling resistor at the PLC terminals to scale the cur-
rent to the equivalent voltage and select the 0 to 20 mA output. For example, install a 500 Ω resistor
across the terminals of a 0 to 10 V input to make the 0 to 20 mA output correspond to 0 to 10V (R =
V/I = 10 V / 0.02 A = 500 Ω). When the GE Multilin TCS2 thermal capacity meter is connected to the
terminals, select the 0 to 1 mA range. Current levels are not affected by the total lead and load resis-
tance which must not exceed 600 Ω for 0-20 mA and 4-20mA range and 2400 Ω for 0-1mA range.
For readings greater than full scale the output will saturate at 21 mA (0-20/4-20 range) or 1.1 mA (0-
1 range). This analog output is isolated. Since both output terminals 18 and 19 are floating, the con-
nection of the analog output to a process input will not introduce a ground loop. Part of the system
should be grounded for safety, typically at the programmable controller. For floating loads, such as a
meter, ground terminal 19 externally. Terminal 20 is internally grounded and may be used as a shield
ground if required. Ground the shield at one end only to prevent ground loop noise.
i) SERIAL PORT (15/16/17)
A serial port provides communication capabilities between the 239 and a remote computer, PLC or
distributed control system (DCS). Up to thirty-two 239 relays can be daisy chained together with 24
AWG stranded, shielded, twisted pair wire on a single communication channel. Suitable wire should
have a characteristic impedance of 120 Ω such as Belden #9841. These wires should be routed
away from high power AC lines and other sources of electrical noise. The total length of the commu-
nications wiring should not exceed 4000 feet for reliable operation. Correct polarity is essential for
the communications port to operate. Terminal 15 (485 A+) of every 239 in a serial communication link
must be connected together. Similarly, terminal 16 (485 B-) of every 239 must also be connected
together. These polarities are specified for a 0 logic and should match the polarity of the master
GE Multilin
Courtesy of NationalSwitchgear.com
5$1*( . Use the TYPE message to select one of the fol-
PROGRAMMED RANGE
0-1 mA
0 mA
1 mA
0 mA
0 A
1A/5A*
0 A
0%
200%
0%
0%
100%
0%
0°C
180°C
0°C
0%
100%
0%
239 Motor Protection Relay
0-20 mA
4-20 mA
20 mA
4 mA
1A/5A*
0A
200%
0%
100%
0%
180°C
0°C
100%
0%
2 INSTALLATION
2
20 mA
1A/5A*
200%
100%
180°C
100%
2-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents