External Connections - GE 239 Instruction Manual

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

2 INSTALLATION
Signal wiring is to box terminals that can accommodate wire as large as 12 gauge. CT connections
are made using #8 screw ring terminals that can accept wire as large as 8 gauge (see Figure 2–3:
TYPICAL WIRING DIAGRAM on page 2–4). A minimal configuration will include connections for
control power, phase CTs and the trip relay. Other features can be wired as required. Considerations
for wiring each feature are given in the sections that follow.
Table 2–2: EXTERNAL CONNECTIONS
CT ROW
1
Phase A CT 5A
2
Phase A CT 1A
3
Phase A CT COM
4
Phase B CT 5A
5
Phase B CT 1A
6
Phase B CT COM
7
Phase C CT 5A
8
Phase C CT 1A
9
Phase C CT COM
10
Ground CT 5A
11
Ground CT 50:0.025
12
Ground CT COM
GE Multilin
Courtesy of NationalSwitchgear.com
SIGNAL LOWER ROW
13
Safety ground
14
Filter ground
15
RS485 A+
16
RS485 B–
17
RS485 ground
18
Analog out +
19
Analog out –
20
Analog out shield
21
Thermistor in +
22
Thermistor com
23
Trip NO
24
Trip COM
25
Trip NC
26
Alarm NO
27
Alarm COM
28
Alarm NC
29
Auxiliary NO
30
Auxiliary COM
31
Auxiliary NC
32
Service NO
33
Service COM
34
Service NC
35
Unused
239 Motor Protection Relay
2 INSTALLATION

2.3 EXTERNAL CONNECTIONS

SIGNAL UPPER ROW
36
Control live (+)
37
Control neutral (–)
38
Sw com
39
Sw com
40
Sw com
41
Sw com
42
Sw com
43
Access sw +
44
Restart sw +
45
Reset sw +
46
Option 1 sw +
47
Option 2 sw +
48
RTD shield
49
RTD1 hot
50
RTD1 comp
51
RTD1 ret
52
RTD2 hot
53
RTD2 comp
54
RTD2 ret
55
RTD3 hot
56
RTD3 comp
57
RTD3 ret
58
Unused