Environmental Type Tests - Siemens RUGGEDCOM RX1400 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1400:
Table of Contents

Advertisement

RUGGEDCOM RX1400
Installation Guide
Test
IEEE 1613.1/
IEC 61000-4-10

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-78
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 60068-1-14
EMC and Environmental Type Tests
Description
Dielectric Strength
Fast Transient (SWC)
Oscillatory (SWC)
Radiated RFI
ESD
Damped Oscillating
Magnetic Field
Description
Cold Temperature
Cold Storage
Dry Heat
Dry Heat Storage
Humidity (Damp Heat, Cyclic)
Humidity (Damp Heat, Steady State)
Vibration
Shock
Seismic
Change of Temperature
DC Power Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Test Ad
Test Ab
Test Bd
Test Bb
Test Db
95% (Non-Condensing), 55 °C (131 °F), 6 cycles
Test Levels
2828 VDC or 2 kV
± 4 kV @ 2.5 kHz, 5 kHz
2.5 kV Common mode @1 MHz
2.5 kV Common Mode
1 kV Differential Mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
100 A/m for 1 s (100 kHz and 1 MHz)
Test Levels
-40 °C (-40 °F), 16 Hours
-40 °C (-40 °F), 16 hours
85 °C (185 °F), 16 Hours
85 °C (185 °F), 16 hours
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
2 g @ 10-150 Hz
30 g @ 11 ms
Method A, Class 2
5 Cycles (-40 to 85 °C or -40 to 185 °F)
Chapter 6
Certification
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents