Chapter 3
Communication Ports
b
In RS-232 mode, ports transmit to DTE (Data Terminal Equipment) devices on pin 2 and receive from DTE devices on pin 3.
Each RS-485 port can communicate with multiple RS-485 devices by wiring devices together in sequence over a
single twisted-pair with transmit and receive signals on the same two wires (half duplex). For reliable, continuous
communication, adhere to the following guidelines:
• To minimize the effects of ambient electrical noise, use shielded cabling.
• The correct polarity must be observed throughout a single sequence or ring.
• The number of devices wired should not exceed 32, and total distance should be less than 1219 m (4000 ft) at
100 kbps.
• The Common terminals should be connected to the common wire inside the shield.
• The shield should be connected to earth ground at a single point to avoid loop currents.
• The twisted pair should be terminated at each end of the chain.
The following shows the recommended RS485 wiring.
2
1
Figure 18: Recommended RS-485 Wiring
1. RUGGEDCOM RX1400 Device    2. Common (Isolated Ground)    3. Negative    4. Positive    5. Shield to Earth (Connected At a Single
Point)    6. RS-485 Devices (32 Total)