7847i-E Installation and Setup Guide
LED COLOR
GREEN
YELLOW
RED
an Unregistered 7847i-E Status Display in Normal Operating State(B)
The sequence below illustrates LED operation when 7847i-E transmits a message.
Figure 14. LED Sequence for a Registered 7847i-E Message Transmission
A-2
Table 6. Status Display Operation
LED LABEL
DESCRIPTION
STATUS
ON – 7847i-E is NOT registered with receiver.
OFF – 7847i-E is registered with receiver.
FAST BLINK – Download session with Compass in progress.
SLOW BLINK – In unison with yellow LED – registration in
MESSAGE
ON – Message transmission pending.
QUICK PERIODIC FLASH – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle, power abnormal.
FAULT
ON – No contact with the network.
OFF– Normal.
SLOW BLINK – Loss of communication with the panel (ECP fault).
FAST BLINK – No network contact AND loss of communication
Figure 13. A Registered 7847i-E Status Display (A) and
progress.
– In unison with green LED , registration in
progress.
with the panel.