Honeywell 7847i-E Installation And Setup Manual page 21

Intranet communication modules
Hide thumbs Also See for 7847i-E:
Table of Contents

Advertisement

PROMPTS
IP2 Supervision
15
30 Day_
Installation Key:
16
**********_
Verify Inst. Key:
17
**********_
Account information is provided by the central station administrator.
Primary City ID
18
(??)_
Primary CS ID
19
(??)
Primary Sub ID
20
(????)
Device Address
21
(12)_
22
Direct Wire
Y/N
(N)_
4204/
ZONE
ENTRY
2-4204
TRIG.
Important Information Regarding Primary (Questions 18-20)
Section 3: Programming the 7847i-E
OPTIONS
If 30 Day or Daily is selected, the 7847i-E will
• 30 Day
send a test alarm to the second CS IP within that
• Daily
interval.
• Full Rate
If Full Rate is selected, a status message is sent
None
to the second CS IP at the same rate as the
regular Supervision Interval (Prompt 24).
NOTE: The second receiver must be
programmed to supervise subscribers in order to
generate the communication failure.
Press the [space] key to scroll through the
choices.
[0-9]
Enter the 10-digit Installation Key necessary for
communication with the receiver. If the key entry
is invalid, the prompt is repeated. See the
Installation Key paragraph in Section 1 for more
information.
Re-enter the 10-digit Installation Key to verify key.
[0-9]
If verification fails, "Verify NOT OK" will be
displayed for one second and the display will
return to the entry of the installation key.
[01-99]
Enter the 2-digit primary city ID, 01-99 (decimal).
[01-FE]
Enter the 2-digit primary central station ID
number, 01-FE (HEX).
Enter the 4-digit subscriber account number,
[0001-9999]
0001-9999 (decimal).
The 7847i-E communicates with the control panel
[01-15]
as a 4204 relay module. Enter the appropriate
address. For VISTA-10P, and FA130CP series
control panels, this must be address 12. For other
controls, see the control panel's Installation and
Setup Guide.
NOTES:
1. The 4204 protocol limits address range to 01-
15. If using 2-4204 mode, the 7847i-E assigns
the second 4204 to the next higher device
address (e.g., if entering address 12 for the first
4204, then address 13 is automatically assigned
to the second 4204 module). Program the
control panel accordingly.
2. The device address(es) must be unique from
the "Keypad Address" entered in Prompt 26 and
any other address used on the control panel.
Applies only to VISTA-128BP/250BP and FBP
[Y], [N]
series controls, and FA1600C and FA1700C
series controls.
Enables Direct Wire Downloading over IP.
If [N], skip to Prompt 24: "Supervision."
DESCRIPTION
3-9