3.4.8.15.
42
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Measured value (MV)
Table 3.4.8.15-1 Configurable MV properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
MV
Class
Addresses
Index
-1 to 65535
Default: -1
Sub-Type
Subtype
Simple
Data Class Spe-
cific
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Scale and Unit
Multiplier
Default: Deka
Phase Number of
Default: 0
Decimals
Scale
Default: None
Unit
Default: Dimensionless
Limit Value Super-
vision
Max
Min
Table 3.4.8.15-2 Additional configurable properties for Sub-Type MV Limit Check
Property/ Para-
Value or Value range/ Default
meter
Sub-Type
MV Limit Check
Limit Value Super-
vision
High
Default: 0
Description
Common data class according to IEC
61850.
Indication index.
MV Sub-type
Data object number for indication.
Specifies the multiplier for current SI unit.
Specifies the number of decimals shown
in HSI. (0..9)
Scale used with this type
SI unit for measurement as described in
IEC 61850
Maximum value for measurement
Minimum value for measurement
Description
MVSubTypeDescription
High limit for measurement. Event is cre-
ated when value crosses the limit.
1MRS756567