Table 3-7
Commissioning sequence with STARTER (example), continued
What to do?
S
4. Save the
Connect with target system (go online)
S
parameters
Target system
on the device
S
Target system
5. The motor
The drives can be started via the control panel in
starts
STARTER.
S
rotating.
This can be done once the pulses have been
enabled for the infeed and line/DC link
identification has been activated. The infeed
then switches to operational mode.
S
Once the pulses are enabled, a one-off motor
data identification run (if activated) is carried out.
S
When the pulses are enabled again,
optimization with a rotating motor (if activated) is
carried out.
STARTER diagnosis options
Under "Component" –> Diagnosis –> Control / status words
S Control / status words
S Parameter status
S Missing enable signals
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Initial commissioning using vector (booksize) as an example
How to do it?
–>
Load to target system
–>
Copy from RAM to ROM
Commissioning
Comments
Position cursor on drive unit
(SINAMICS S120) and
right-click.
For more information about
the control panel, see Getting
Started.
During motor identification, a
current flows through the
motor, which means that it
can align itself by up to a
quarter of a revolution.
For more information about
line/DC link identification and
motor identification, see the
Function Manual.
3-65