Basic Information about the Drive System
Inputs/outputs
7.8.2

Digital inputs/outputs

Digital inputs
+
Fig. 7-10
Properties
S The digital inputs are "high-active".
S An open input is interpreted as "low".
S Fixed debouncing setting
Delay time = 1 to 2 current controller cycles (p0115[0])
S Availability of the input signal for further interconnection
– inverted and not inverted as a binector output
– as a connector output
S Simulation mode settable and parameterizable.
S CU 320: Isolation block by block, set by jumper.
– Jumper open
The digital inputs function only if a reference ground is connected.
– Jumper closed
The reference potential of the digital inputs is the ground of the Control Unit.
S Sampling time for digital inputs/outputs adjustable on CU320 (p0799)
7-256