208 Actual signals and parameters
All parameters
No.
Name/Value
COMM
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
1609 START
ENABLE 2
1610 DISPLAY
ALARMS
NO
YES
1611 PARAMETER
VIEW
DEFAULT
FLASHDROP
1612 FAN
CONTROL
Description
Fieldbus interface as the source for the inverted Start
enable (Start disable) signal, ie control word
WORD 2
bit 18 (bit 19 for Start enable 2). The control word
is sent by the fieldbus controller through the fieldbus
adapter or embedded fieldbus (Modbus) to the drive. For
the control word bits, see section
profile
on page 320.
Note: This setting applies only for the DCU profile.
External signal required through inverted digital input DI1. 0
= Start enable. If Start enable signal is switched off, the
drive will not start or it coasts to stop if it is running and
alarm
START ENABLE 1 MISSING
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Selects the source for the Start enable 2 signal. See
parameter
1608 START ENABLE
See parameter
1608 START ENABLE
Activates/deactivates alarms
OVERVOLTAGE
(2002),
DEVICE OVERTEMP
chapter
Fault tracing
Alarms are inactive.
Alarms are active.
Selects the parameter view, ie which parameters are shown.
Note: This parameter is visible only when it is activated by
the optional FlashDrop device. FlashDrop is designed for
fast copying of parameters to unpowered drives. It allows for
easy customization of the parameter list, eg selected
parameters can be hidden. For more information, see
MFDT-01 FlashDrop user's manual (3AFE68591074
[English]).
FlashDrop parameter values are activated by setting
parameter
9902 APPLIC MACRO
Complete long and short parameter lists
FlashDrop parameter list. Does not include short parameter
list. Parameters which are hidden by the FlashDrop device
are not visible.
Selects the fan to be switched on and off automatically or
keeps the fan on all the time.
When the drive is used in ambient temperatures of 35 °C
and above, it is recommended to have the cooling fan
always on (selection ON).
DCU communication
(2021) is activated.
1.
1.
OVERCURRENT
UNDERVOLTAGE
(2009). For more information, see
on page 335.
to 31
(LOAD FD
Def/FbEq
7
0302 FB CMD
-1
-2
-3
-4
-5
NOT SEL
(2001),
NO
(2003) and
0
1
DEFAULT
SET).
0
1
AUTO