Protection
8.2 Configuring access protection for the CPU
Properties of the access levels
Each access level allows unrestricted access to certain functions without entering a
password, e.g. identification using the "Accessible devices" function.
The CPU's default setting is "No restriction" and "No password protection". In order to protect
access to a CPU, you must edit the properties of the CPU and set up a password. In the
default access level "Full access (no protection)" every user can read and change the
hardware configuration and the blocks. A password is not set and is also not required for
online access.
Communication between the CPUs (via the communication functions in the blocks) is not
restricted by the access level of the CPU, unless PUT/GET communication is deactivated in
the "No access" (complete protection) access level.
Entry of the right password allows access to all the functions that are allowed in the
corresponding level.
Not e
Conf iguring an access level does not replace know-how protection
Configuring access levels offers a high degree of protection against unauthorized changes
on the CPU by restricting the rights to download the hardware and software configuration to
the CPU. However, blocks on the SIMATIC memory card are not write- or read-protected.
Use know-how protection to protect the code of blocks on the SIMATIC memory card.
Behavior of functions with different access levels
The STEP 7 online help includes a table which lists the online functions that are available in
the different access levels.