Standard Functions
NOTE:. Parameters marked with " " in A column are accessible even in inverter running.
Parameters marked with " " in B column are accessible even in inverter running when in
the high level access mode, which means that b031 is set to "10".
Func.
Name
Code
A001
Frequency source
A201
Frequency source,
nd
2
motor
A002
Run command source
A202
Run command source,
nd
2
motor
A003
Base frequency
A203
Base frequency,
nd
2
motor
A004
Maximum frequency
A204
Maximum frequency,
nd
2
motor
A005
[AT] selection
A011
[O] input active range
start frequency
"A" Function
Description
Eight options; select codes:
00...POT on ext. operator
*Valid when connecting the
OPE-SR/SRmini
01...Control terminal
*Set to "01" when connecting
the WJ-VL or External volume
via control terminal
02...Function F001 setting
03...Modbus network input
04...Option
06...Pulse train input
07...via EzSQ
10...Calculate function output
Four options; select codes:
01...Control terminal
02...Run key on keypad, or
digital operator
03...Modbus network input
04...Option
Settable from 30 Hz to the
maximum frequency(A004)
Settable from 30 Hz to the 2
maximum frequency(A204)
Settable from the base
frequency to 400(580)
Settable from the 2
frequency to 400(580)
Three options; select codes:
00...Select between [O] and
[OI] at [AT] (ON=OI,
OFF=O)
02...Select between [O] and
external POT at [AT]
(ON=POT, OFF=O)
03...Select between [OI] and
external POT at [AT]
(ON=POT, OFF=OI)
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to
*1
400.0(580.0)
A
nd
*1
Hz
nd
base
*1
Hz
56
Defaults
B
Initial data
01
01
01
01
50.0
50.0
50.0
50.0
00
0.00
Units
Hz
Hz
Hz
Hz
Hz

Hide quick links: